[SIL-228] Connection rejected for S7-400 controllers installed in slot 2

parent 2458f5e3
No related branches found
No related tags found
No related merge requests found
...@@ -25,6 +25,9 @@ namespace Silecs ...@@ -25,6 +25,9 @@ namespace Silecs
SNAP7Connection::SNAP7Connection(PLC* thePLC) : Connection(thePLC) SNAP7Connection::SNAP7Connection(PLC* thePLC) : Connection(thePLC)
{ {
rackNb_ = 0; //rackNb - common rack is 0 so far
slotNb_ = -1; //slotNb - depends on hardware configuration (scan is required the first connect)
recvClient_ = Cli_Create(); recvClient_ = Cli_Create();
sendClient_ = Cli_Create(); sendClient_ = Cli_Create();
LOG(ALLOC) << "SNAP7Connection (create) PLC/Cluster: " << thePLC->getName() << "/" << thePLC->theCluster_->getClassName(); LOG(ALLOC) << "SNAP7Connection (create) PLC/Cluster: " << thePLC->getName() << "/" << thePLC->theCluster_->getClassName();
...@@ -40,14 +43,17 @@ namespace Silecs ...@@ -40,14 +43,17 @@ namespace Silecs
bool SNAP7Connection::open(PLC* thePLC) bool SNAP7Connection::open(PLC* thePLC)
{ {
int err = 0; int err = 0;
bool ret = false;
int slotNb;
//Slot number is not required, so try to connect on different slots (1..31), depending on hardware layout. //Slot number is not required, so try to connect on different slots (1..31), depending on hardware layout.
int *slotsScan; int *slotsScan;
int slotsS7400[4] = { 3,4,2,1 }; //slot scan - most common layout S7-400 int slotsS7400[4] = { 3,2,4,1 }; //slot scan - most common layout S7-400
int slotsS71x00[4] = { 1,2,3,4 }; //slot scan - most common layout S7-1200, S7-1500 int slotsS71x00[4] = { 1,2,3,4 }; //slot scan - most common layout S7-1200, S7-1500
int slotsDefault[4] = { 2,3,4,1 }; //slot scan - most common layout S7-other (S7-300, ET200S) int slotsDefault[4] = { 2,3,4,1 }; //slot scan - most common layout S7-other (S7-300, ET200S)
int rackNb = 0; //rackNb - common rack is 0 so far int nbMaxSlot = ((slotNb_ == -1) ? 4 : 1); //slots scan only the first time (slotNb_ == -1)
int slotNb;
switch (thePLC->getModelID()) switch (thePLC->getModelID())
{ {
...@@ -60,27 +66,36 @@ namespace Silecs ...@@ -60,27 +66,36 @@ namespace Silecs
slotsScan = slotsDefault; //S7-300, ET200S slotsScan = slotsDefault; //S7-300, ET200S
} }
for(int i=0; i<4; i++) for(int i=0; i<nbMaxSlot; i++)
{ {
slotNb = slotsScan[i]; slotNb = slotsScan[i];
err = Cli_ConnectTo(recvClient_, thePLC->getIPAddress().c_str(), rackNb, slotNb);
if (err) // next slot err = ((slotNb_ == -1) ? Cli_ConnectTo(recvClient_, thePLC->getIPAddress().c_str(), rackNb_, slotNb) :
{ Cli_Connect(recvClient_));
LOG(DEBUG) << "SNAP7 connection (channel-2) failed on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb << "/" << slotNb <<". SNAP7[" << err << "]: " << getSNAP7ErrorMessage(err);
break; if (err == 0)
}
LOG(DEBUG) << "SNAP7 connect (channel-1) successful on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb << "/" << slotNb;
//We managed to open the first channel, just open the second one on the same slot.
err = Cli_ConnectTo(sendClient_, thePLC->getIPAddress().c_str(), rackNb, slotNb);
if (err) // next slot
{ {
LOG(DEBUG) << "SNAP7 connection (channel-2) failed on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb << "/" << slotNb <<". SNAP7[" << err << "]: " << getSNAP7ErrorMessage(err); LOG(DEBUG) << "SNAP7 connect (channel-1) successful on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb_ << "/" << slotNb;
break;
//We managed to open the first channel, just open the second one on the same slot.
err = ((slotNb_ == -1) ? Cli_ConnectTo(sendClient_, thePLC->getIPAddress().c_str(), rackNb_, slotNb) :
Cli_Connect(sendClient_));
if (err != 0)
{
LOG(DEBUG) << "SNAP7 connection (channel-2) failed on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb_ << "/" << slotNb <<". SNAP7[" << err << "]: " << getSNAP7ErrorMessage(err);
continue;
}
LOG(DEBUG) << "SNAP7 connect (channel-2) successful on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb_ << "/" << slotNb;
slotNb_ = slotNb; //connection is ok we can store the valid slot number for the next (re)connection (will be faster).
ret = true;
break;
} }
LOG(DEBUG) << "SNAP7 connect (channel-2) successful on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb << "/" << slotNb; LOG(DEBUG) << "SNAP7 connection (channel-1) failed on PLC/rack/slot: " << thePLC->getName() << "/" << rackNb_ << "/" << slotNb <<". SNAP7[" << err << "]: " << getSNAP7ErrorMessage(err);
return true;
} }
return false; return (ret);
} }
......
...@@ -55,6 +55,9 @@ namespace Silecs ...@@ -55,6 +55,9 @@ namespace Silecs
bool open(PLC* thePLC); bool open(PLC* thePLC);
bool close(PLC* thePLC); bool close(PLC* thePLC);
int rackNb_; //rackNb - common rack is 0 by default
int slotNb_; //slotNb - depends on hardware configuration (scan is required the first connect)
std::string getSNAP7ErrorMessage(int err); std::string getSNAP7ErrorMessage(int err);
}; };
......